operating service: ....................................................... 70º C
short - circuit (5 s.) : ........................................................ 160º C
ESO7Z1-K (AS)........................................................ 2500 V. (15 min.)
According to UNE 211002 standard.
1. Flexible electrolytic copper conductor class 5 according to UNE-EN 60228/ EN 60228 /IEC 60228 standard.
2.Thermoplastic polyolefine insulation HFFR type T1Z1 according toUNE 211002 ANEXO 1.
T. minimum ºC: +5
T. maximum ºC: +40 (1)
(1) Exposed to the sun, the temperature of the surface of the cable can exceed the value given, but limited to a maximum of 60oC.
The composition of the isolation of thermoplastic polyolefine HFFR type TIZ1, guarantees the non-flame propagation of
the flame according to: UNE-EN 60332-2-1 ; EN 60332-2-1 ; IEC 60332-2-1 standards.
According to UNE EN 50266-2-4/EN 50266-2-4/IEC 60332-3;UNE EN 50266-2-5/EN 50266-2-5/IEC 60332-3 standards.
In case of fire, avoids loss of visibility due to smoke produced by cable combustion, according to UNE EN 61034-2 / EN 61034-2 / IEC 61034-2 standards.
In case of fire, the emission of monoxide of carbon, carbon dioxide and hydrochlorate acid is lower to 0.5 %, according to: UNE EN 50267-2-1/ EN 50267-2-1 / IEC 60754-1 standards.
In case of fire, the index acidity and the conductivity the emanated gases according to UNE EN 50267-2-3 / EN 50267-2-3 / IEC 60754-2+A1 standards. minimum PH > 4,3 / maximum conductivity (µS/cm) <100.