operating service: ........................................................ 90º C
short - circuit (5 s.) : .................................................... 250º C
Alternating current ...................................................... 3.5 kV.
Direct current ............................................................... 8.5 kV.
Built according to EA-025 standard:
1. Flexible electrolytic copper conductor class 5 according to UNE-EN 60228/ EN 60228 /IEC 60228 standard.
2.Isolation made of a special cross-linked halogen free compound.
3. Polyolefine stuffed(for multi-core from 10 mm2 section).
4. Polyolefine inner sheath according to UNE 21123-4 annexed 1 index 1.
5. Double steel wire armour (or aluminium for a single-core cables) Applied in helix form.
6. Outer polyolefine sheath according to UNE 21123-4 annexed 1 table1.
The identification of the conductors will be made according to UNE 21089-1
Minimum temperature allowed for the cable laying during its installation and assembly of accessories: 0ºC
The composition of the isolation of thermoplastic polyolefine, guarantees the non-flame propagation of the flame according to: UNE-EN 60332-2-1 ; EN 60332-2-1 ; IEC 60332-2-1 standards.
According to UNE EN 50266-2-4 / EN 50266-2-4 / IEC 60332-3 ; UNE EN 50266-2-5 / EN 50266-2-5 / IEC 60332-3 standards.
In case of fire, avoids loss of visibility due to smoke produced by cable combustion, according to UNE EN 61034-2 / EN 61034-2 / IEC 61034-2 standards.
In case of fire, the emission of monoxide of carbon, carbon dioxide and hydrochlorate acid is lower to 0.5 %, according to: EN 50267-2-3 / EN 50267-2-3 / IEC 60754-2+A1. PH mínimo ≥ 4,3 / Conductividad máxima (µS/cm) ≤ 100.
In case of fire, the emission of monoxide of carbon, carbon dioxide and hydrochlorate acid is lower to 0.5 %, according to: UNE EN 50267-2-1/ EN 50267-2-1 / IEC 60754-1 standards.
According to UNE-EN 50362 / EN 50362 standards.
* For cables of diameter over 20 mm or nominal cross section over 2.5 mm2. UNE EN 50362 standard will be applied. .