Direct current.............................................................. 8.5 kV.
Built according to UNE 21123-4:
1. Flexible electrolytic copper conductor class 5 according to UNE-EN 60228/ EN 60228 /IEC 60228 standard.
2. XLPE cross-linked polyethilene insulation type DIX 3 according to UNE HD 603-1 index 2A
3. Polyolefine sheath according to UNE 21123-4
They appear in formations: phase, neutral, protection and the conductor of section 1.5 (red isolation) for control
Minimum temperature allowed for the cable laying during its installation and assembly of accessori 0ºC
The composition of the isolation of thermoplastic polyolefine, guarantees the non-flame propagation of the flame according to: UNE-EN 60332-2-1 ; EN 60332-2-1 ; IEC 60332-2-1 standards.
According to UNE EN 50266-2-4 / EN 50266-2-4 / IEC 60332-3 ; UNE EN 50266-2-5 / EN 50266-2-5 / IEC 60332-3 standards.
In case of fire, avoids loss of visibility due to smoke produced by cable combustion, according to UNE EN 61034-2 / EN 61034-2 / IEC 61034-2 standards.
In case of fire, the emission of monoxide of carbon, carbon dioxide and hydrochlorate acid is lower to 0.5 %, according to: UNE EN 50267-2-1/ EN 50267-2-1 / IEC 60754-1 standards.
In case of fire, the index acidity and the conductivity the emanated gases according to UNE EN 50267-2-3 / EN 50267-2-3 / IEC 60754-2+A1 standards. minimum PH ≥ 4,3 / maximum conductivity (µS/cm) ≤100.
It provides an optimal protection before possible environmental agents, allowing its outdoor installation, underground, even in the presence of non permanent humidity.