afirenas l as
tabla de capacidad de bobinas tabla de capacidad de bobinas tabla de capacidad de bobinas afirenas l as
  • designacion tecnica ES05Z1-K (AS) / H07Z1-K (AS)
  • tension nominal
  • ES05Z1-K(AS) ............................................. 300/500 V(hasta 1mm2)
  • H07Z1-K(AS) ................................ 450/750 V(a partir de 1.5 mm2)
  • temperatuta maxima de servicio
  • operating service: ....................................................... 70º C
  • short - circuit (5 s.) : .................................................... 160º C
  • tension de ensayo
  • H07Z1-K ......................................................... 2500 V (15 min.)
  • descripcion constructiva According to UNE 211002 standard.
  • 1. Flexible electrolytic copper conductor class 5 according to UNE-EN 60228/ EN 60228 /IEC 60228 standard.
  • 2. Thermoplastic isolation of polyolefine HFFR type TIZ1 according to UNE 211002 ANEXO 1 standard.
  • These cables are always single core
  • Rango de Temperaturas de almacenaje, transporte y manejo
  • T. minimum ºC: +5
  • T. maximum ºC: +40 (2)
  • (1)160ºC for sections up to 300 mm2, 140ºC for sections over 300 mm2.
    (2) Exposed to the sun, the temperature of the surface of the cable can exceed the value given, but limited a maximum of 60ºC.
  • no propagador de la llama
  • The composition of the isolation of thermoplastic polyolefine HFFR type TIZ1, guarantees the non-flame propagation of the flame according to: UNE-EN 60332-2-1 ; EN 60332-2-1 ; IEC 60332-2-1 standards.
  •  no propagacion del incendio
  • According to UNE EN 50266-2-4 / EN 50266-2-4 / IEC 60332-3 ; UNE EN 50266-2-5 / EN 50266-2-5 / IEC 60332-3 standards.
  •  densidad emision de humos
  • In case of fire, avoids loss of visibility due to smoke produced by cable combustion, according to UNE EN 61034-2 / EN 61034-2 / IEC 61034-2 standards.
  • determinacion de halogenos
  • In case of fire, the emission of monoxide of carbon, carbon dioxide and hydrochlorate acid is lower to 0.5 %, according to: UNE EN 50267-2-1/ EN 50267-2-1 / IEC 60754-1 standards.
  • acidez y corrosividad de los gases
  • In case of fire, the index acidity and the conductivity the emanated gases according to UNE EN 50267-2-3 / EN 50267-2-3 / IEC 60754-2+A1 standards. minimum PH > 4,3 / maximum conductivity (µS/cm) <100.<100.
  • flexibilidad
  • The use of flexible copper conductor (class 5) forming a rope yarn of several very fine threads in combination with the isolation of thermoplastic polyolefine HFFR type TIZ1 equips these cables with exceptional degrees of flexibility.
  • The composition of the sheath, guarantees an optimal sliding, enabling an easier installation.