operating service: ....................................................... 60º C
short - circuit (5 s.) : .................................................... 150º C
H05Z1Z1-F ......................................................... 2000 V (5 min.)
According to UNE 21031-14:
1. Flexible electrolytic copper conductor class 5 according to UNE-EN 60228/ EN 60228 /IEC 60228 standard.
2. Isolation mixture of thermoplastic material type TI6, according to UNE 21031-14 standard.
3. Sheath mixture of thermoplastic material type TM7, according to UNE 21031-14 standard.
They appear in multi-core formation of 2 to 5 insulated phases, depending on the installation necessities.
T. minimum ºC: +5
T. maximum ºC: +40 (1)
(1) Exposed to the sun, the temperature of the surface of the cable can exceed the value given, but limited to a maximum of 60ºC.
The use of flexible copper conductor forming a rope yarn of several very fine threads in combination with the isolation and sheath type TM7 equips these cables with an exceptional degree of flexibility.
The composition of the isolation of PVC type TM7, guarantees the non-flame propagation of the flame according to UNE-EN 60332-2-1 ; EN 60332-2-1 ; IEC 60332-2-1 standards.
Standard UNE 21176 recommends its use for light mobile services, extra light, ordinary even staying temporarily outdoors.
Use condition AD2 (Probability of rain drops falling vertically) according to UNE 21176 ANEXO C.
Condition of use AF3 (subject of intermittent or accidental form to corrosive or polluting substances) according to UNE. 21176 ANEXO C standards.
In case of fire, avoids loss of visibility due to smoke produced by cable combustion, according to UNE EN 61034-2 / EN 61034-2 / IEC 61034-2 standards.
In case of fire, the emission of monoxide of carbon, carbon dioxide and hydrochlorate acid is lower to 0.5 %, according to: UNE EN 50267-2-1/ EN 50267-2-1 / IEC 60754-1 standards.
In case of fire, the index acidity and the conductivity the emanated gases according to UNE EN 50267-2-3 / EN 50267-2-3 / IEC 60754-2+A1standards. minimum PH > 4,3 / maximum conductivity (µS/cm) <100.