H05V2-U .................................................................... 300/500 V.
H07V2-U/R ................................................................. 450/750 V.
operating service: ............................................................. 90º C
short - circuit (5 s.) : ......................................................... 160º C
H05V2-U ............................................................. 2000 V. (15 min.)
H07V2-U/R .......................................................... 2500 V. (15 min.)
According to UNE 21031-7
1. Solid electrolytic copper conductor class 1 (H05V2-U/ H07V2-U) & class 2 ( H07V2-R). according to UNE-EN 60228/ EN 60228 /IEC 60228.
2. PVC insulation type TI 3 according to UNE 21031-1
These cables are always single-core.
T. minimum ºC: +5
T. maximum ºC: +40 (1)
(1) Exposed to the sun, the surface temperature of the cable can exceed the value given, but limited to a maximum of 60ºC.
The composition of the isolation of PVC type TI3, guarantees non-falme propagation according to standard requirements: UNE-EN 60332-2-1 ; EN 60332-2-1 ; IEC 60332-2-1
Optimum sliding characteristic. Guarantees an optimal sliding, reducing the time of installation.