operating service: ........................................................ 90º C
short-circuit (5 s.) : ...................................................... 250º C
Alternating current ..................................................... 3.5 kV.
Direct current .............................................................. 8.5 kV.
Built according to UNE 21123-2
1. Flexible electrolytic copper conductor class 5 according to UNE-EN 60228/ EN 60228 /IEC 60228 standard.
2. XLPE insulation type DIX 3 according to UNE HD 603-1 index 2A.
3. Stuffed of PVC (for multicore from 10 mm2 size).
4. PVC inner sheath type DMV-18 according to UNE HD 603-1 index 4A standard.
5.Steel wire galvanized armour index.
6. PVC outer sheath type DMV-18, according to UNE HD 603-1 index 4A.
They appear in single-core formation and multicore of 1 to 5 insulated phases, depending on the installation necessities.
Minimum temperature allowed for the cable laying during its installation and assembly of accessories: 0ºC
The application of a double steel wire armour (or aluminum for the single-core ones) offers an excellent protection against accidental blows, crushing or possible perforations.
The steel wire galvanized armour allows the cable stay under permanent tensile stress.
The composition of the isolation of PVC type DMV-18, guarantees non-flame porpagation according to UNE-EN 60332-2-1 ; EN 60332-2-1 ; IEC 60332-2-1 standards.
According to UNE EN 50266-2-4 / EN 50266-2-4 / IEC 60332-3 ; UNE EN 50266-2-5 / EN 50266-2-5 / IEC 60332-3 standards.
The isolation of XLPE, improves the capacity of power transmission, elevating temperature in permanent service up to 90ºC and short - circuit (5 s.) up to 250ºC, in contrast with 70/160ºC of PVC.
It provides an optimal protection before possible environmental agents, allowing its outdoor installation, underground, even in the presence of non permanent humidity.