operating service: ............................................................ 60º C
short - circuit (5 s.) : ........................................................ 150º C
H05VV5-F ......................................................... 2000 V (5 min.)
According to UNE 21031-13
1. Flexible electrolytic copper conductor class 5 according to UNE-EN 60228/ EN 60228 /IEC 60228 standard.
2. PVC insulation type TI 2 according to UNE 21031-1.
3. PVC outer sheath, special nitroxil / PVC compound type TM 5 according to UNE 21031-1.
They appear in multi core formation of 2 to 5 isolated phases of 1 mm2.
T. minimum ºC: +5
T. maximum ºC: +40 (1)
(1) Exposed to the sun, the surface temperature of the cable can exceed the value given, but limited to a maximum of 60oC.
The use of flexible copper conductor forming a rope yarn of some very fine threads in the combination with the isolation equips these cables with exceptional degrees of flexibility.
The composition of the isolation of PVC type TM5, guarantees the non flame propagation according to UNE-EN 60332-2-1 ; EN 60332-2-1 ; IEC 60332-2-1 standards.
Standard UNE 21176 recommends its use for light mobile services, extra-light, ordinary even staying temporarily outdoors.
Use condition AD2 (probability of rain drops falling vertically) according to UNE 21176 ANEXO C standard.
Its presence is allowed in mineral oils according to EN 60811-2-1(*).
(*) The Barryflex-oil cables fulfill the exigencies of the norm IN 60811-2-1 in section 10 (Test of resistance to the mineral oil, for covers). This norm specifies for the resistance
test a mineral oil with the following characteristics: - aniline Point: 93OC+-3OC (colorant additive of habitual use in oils and varnishes for wood); - Viscosity to 100 OC:
20 centistokes + - 1 centistokes; - Flash point: 245OC +-6OC.v. In most of oils of industrial use, we found inferior values (less aggressive) to the determined ones for the test.
Any type of oil, whose characteristics surpass the indicated ones, would entail a variation of the conditions of test, not being able to make sure the integrity of the cable
in the presence of this oil. In such case it must be consulted with cable manufacturer.