operating service: ............................................................ 90º C
short - circuit (5 s.) : ........................................................ 250º C
Alternating current .......................................................... 3.5 kV.
Direct current .................................................................. 8.5 kV.
Built according to UNE 21123-2 standard:
Solid electrolytic copper conductor class 1 and/or 2 according to UNE-EN 60228/ EN 60228 /IEC 60228 standard.
XLPE-polyethylene isolation cross-linked type DIX 3 according to UNE HD 603-1 index 2A.
Sheath of PVC Dmv-18 type according to UNE HD 603-1 table 4A
They appear in single-core formation and multicore of 1 to 5 insulated phases, depending on the installation requirements.
Minimum temperature allowed for the cable laying during its installation and assembly of accessories:
The composition of the isolation of PVC type DMV-18, guarantees non flame propagation according to: UNE-EN 60332-2-1 ; EN 60332-2-1 ; IEC 60332-2-1 standards.
It offers a good protection face to possible environmental agents, allowing its installation outdoors, under earth, even in the presence of non-permanent humidity.
The isolation of XLPE, improves the capacity of power transmission, when elevating the permanent service temperature up to 90º C. and short-circuit (5 s.) up to 250 ºC, contrary to 70/160º C of PVC.