afirenas dix as
tabla de capacidad de bobinas tabla de capacidad de bobinas tabla de capacidad de bobinas afirenas dix as
  • designacion tecnica DI-X RZ1-K(AS) 0.6/1 kV
  • tension nominal
  • 0.6/1 kV
  • temperatuta maxima de servicio
  • operating service: ....................................................... 90º C
  • short-circuit (5 s.) : ..................................................... 250º C
  • tension de ensayo
  • Alternating current..................................................... 3.5 kV.
  • Direct current.............................................................. 8.5 kV.
  • descripcion constructivaBuilt according to UNE 21123-4:
  • 1. Flexible electrolytic copper conductor class 5 according to UNE-EN 60228/ EN 60228 /IEC 60228 standard.
  • 2. XLPE cross-linked polyethilene insulation type DIX 3 according to UNE HD 603-1 index 2A
  • 3. Polyolefine sheath according to UNE 21123-4
  • They appear in formations: phase, neutral, protection and the conductor of section 1.5 (red isolation) for control
  • Minimum temperature allowed for the cable laying during its installation and assembly of accessori 0ºC
  • ensayo de propagacion de la llama
  • The composition of the isolation of thermoplastic polyolefine, guarantees the non-flame propagation of the flame according to: UNE-EN 60332-2-1 ; EN 60332-2-1 ; IEC 60332-2-1 standards.
  • ensayo de propagacion del incendio
  • According to UNE EN 50266-2-4 / EN 50266-2-4 / IEC 60332-3 ; UNE EN 50266-2-5 / EN 50266-2-5 / IEC 60332-3 standards.
  • densidad de humos
  • In case of fire, avoids loss of visibility due to smoke produced by cable combustion, according to UNE EN 61034-2 / EN 61034-2 / IEC 61034-2 standards.
  • determinacion de halogenos
  • In case of fire, the emission of monoxide of carbon, carbon dioxide and hydrochlorate acid is lower to 0.5 %, according to: UNE EN 50267-2-1/ EN 50267-2-1 / IEC 60754-1 standards.
  • acidez y corrosividad de los gases
  • In case of fire, the index acidity and the conductivity the emanated gases according to UNE EN 50267-2-3 / EN 50267-2-3 / IEC 60754-2+A1 standards. minimum PH ≥ 4,3 / maximum conductivity (µS/cm) ≤100.
  • comportamiento a la intemperie
  • It provides an optimal protection before possible environmental agents, allowing its outdoor installation, underground, even in the presence of non permanent humidity.